Final | 11/1/2010 | 11/2/2010 | 11/2/2010 | A | PASS |
Daryl DeGrange
|
|
|
Bob we have made the applicable corrections that you ask for, let me know if you have any questions thank you Phone #: ###-#### >> Inspection requested via web by Brad ok final
|
Final | 10/28/2010 | 10/29/2010 | 10/29/2010 | A | FAIL |
Bob Reichert
|
|
|
brad Phone #: ###-#### called, left correction notice, NEC 410.62(C) shall provide grounding type attachment plugs to electric discharge luminaires, 422,52 drinking fountains shall be gfci protected, 600.5 shall provide sign circuit, 20A dedicated, 330.30(B) shall secure mc cable within 12" of termination, BCC shall provide access to areas with electrical items for inspection, NOTE: corrections shall be made within 5 working days
|
ELE-Aging Inspection | 8/16/2010 | 8/16/2010 | 8/16/2010 | | DONE |
Bob Reichert
|
|
|
see doc expire
|
DOC - Permit Expired | 8/16/2010 | 8/16/2010 | 8/16/2010 | P | PASS |
Bob Reichert
|
|
|
no activity
|
ELE-Aging Inspection | 6/14/2010 | 6/14/2010 | 6/18/2010 | | DONE |
Bob Reichert
|
|
|
suc
|
Conference | 11/17/2009 | 11/17/2009 | 11/17/2009 | P | DONE |
Doug A Poedy
|
|
|
Doug please call me to set a time to meet at the job to discuss some changes. Thank you Phone #: ###-#### Internet Inspection Request from: Brad Baker
|
Electrical Rough-In | 10/5/2009 | 10/6/2009 | 10/6/2009 | A | PASS |
Doug A Poedy
|
|
|
(ceiling will remain open) walls need approval for cover thank you Phone #: ###-#### Internet Inspection Request from: Brad Baker. Ok to cover walls.
|