ELE-Aging Inspection | 2/2/2011 | 2/2/2011 | 2/2/2011 | | CANC |
Daryl DeGrange
|
|
|
|
Final | 2/2/2011 | 2/2/2011 | 2/2/2011 | A | PASS |
Daryl DeGrange
|
|
|
final ok
|
ELE-Aging Inspection | 12/3/2010 | 12/3/2010 | 12/7/2010 | | DONE |
Daryl DeGrange
|
|
|
suc no activity
|
Permanent Service | 10/7/2009 | 10/8/2009 | 10/8/2009 | A | PASS |
Doug A Poedy
|
|
|
Larry Phone #: ###-####. P/S O/H Reconnect ok.
|
Permanent Service | 10/5/2009 | 10/5/2009 | 10/5/2009 | P | FAIL |
Bob Reichert
|
|
|
larry Phone #: ###-#### called, left correction notice,NEC 230.24(A) conductors shall be 8' above roof, 250.52(A) shall utilize interior metal water pipe within 5' of entering building for gec, 250.56 shall install 2 ground rods minimum 6' apart, no esc this project
|
Permanent Service | 10/1/2009 | 10/1/2009 | 10/1/2009 | P | CANC |
Doug A Poedy
|
|
|
Larry Phone #: ###-####-cancel per Larry Hoff phone call 10:30am BAS
|