Final | 10/28/2009 | 10/29/2009 | 10/29/2009 | P | PASS |
Bob Reichert
|
|
|
Jeff Pierce(alternate ph# ###-####) Phone #: ###-#### Internet Inspection Request from: Dave Friend corrections made, ric ok, ok to final, no esc this project
|
Conference | 10/20/2009 | 10/21/2009 | 10/21/2009 | A | CANC |
Bob Reichert
|
|
|
Jeff Pierce Phone #: ###-#### Internet Inspection Request from: Dave Friend see ri
|
Electrical Rough-In | 10/21/2009 | 10/21/2009 | 10/21/2009 | A | FAIL |
Bob Reichert
|
|
|
Jeff Pierce Phone #: ###-#### Internet Inspection Request from: Dave Friend met contractot, left correction notice to owner, NEC 358.30 emt shall be securely fastened within 3' of termination, 725.25 abandoned low voltage cables shall be removed, 300.11(A) cables shall not be supported by ceiling, BCC no violations shall be retained
|
Electrical Rough-In | 10/20/2009 | 10/20/2009 | 10/20/2009 | P | PASS |
Bob Reichert
|
|
|
Jeff Pierce Phone #: ###-#### Internet Inspection Request from: Dave Friend walls only ok to cover
|