Temporary Service | 10/27/2009 | 10/28/2009 | 10/28/2009 | P | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### Internet Inspection Request from: Stephen Kren. T/S U/G Connect ok.
|
Temporary Service | 10/26/2009 | 10/27/2009 | 10/27/2009 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Stephen Kren called, left correction notice, NEC 250.53(G) upper end of electrode shall be flush with or below ground, 230.70 shall provide means to disconnect all conductors, 406.8(B) 15 and 20a receptacles shall be listed weather resistant type, no esc this project
|