Permit Information
Permit NumberELE09-02099
StatusFinaled
Name MISSMAN ELECTRIC CO INC
Site Address 317 N LATAH ST
Project Name 
Customer Number384-4391
ePlanReview 
Description
Electrical Permit - Alteration: Install new service and tvss rewire vfd controls and pumps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/19/20102/22/20102/22/2010APASS
DetailsJack Frank
Please call Dave at number above if door is not unlocked. Thank You. Inspection requested from web by: Scott Abbott Phone #: ###-#### ok
Final2/17/20102/18/20102/18/2010PFAIL
DetailsJack Frank
PLEASE CALL DAVE AT NUMBER ABOVE IF YOU HAVE ANY TROUBLE GAINING ACCESS. DOOR SHOULD BE UNLOCKED. Inspection requested from web by: Scott Abbott Phone #: ###-#### needs GEC to water from p/s and x former, bushings for 4 and larger, plastic conn for GEC, and #4 for all 200 amp bonding
Permanent Service1/25/20101/26/20101/26/2010APASS
DetailsBob Reichert
Meter base was changed since service was approved so need new inspection and sticker for IPCO connect. Phone #: ###-#### Internet Inspection Request from: Scott Abbott new meter base, p/s o/h n ok, no esc this project
Rough-In Permanent Service1/15/20101/19/20101/19/2010ACANC
DetailsBob Reichert
Please call Dave at ###-#### for location and key to unlock the door Phone #: ###-#### Internet Inspection Request from: Scott Abbott see p/s, no esc this project
Permanent Service1/19/20101/19/20101/19/2010APASS
DetailsBob Reichert
Please call Dave at ###-#### for location and key to unlock the door Phone #: ###-#### Internet Inspection Request from: Scott Abbott p/s o/h n ok, no esc this project
Conference12/29/200912/30/200912/30/2009ADONE
DetailsBob Reichert
We will have cans hung on wall and would like to consult with you do to tight clearances could you please call Danny Smith at ###-#### with a time to meet you Phone #: ###-#### Internet Inspection Request from: Scott Abbott reviewed clearance for electrical equipment, said ok to mount surge protector and voltage protector over tansformer and service gear as required, no esc this project
Electrical Rough-In10/28/200910/30/200910/30/2009APASS
DetailsBob Reichert
underground uffer and pvc to pump concrete schudule to pour Monday Phone #: ###-#### Internet Inspection Request from: Scott Abbott called contractor, ok to pour, u/g at pad ok to pour, no esc this project