Final | 4/20/2010 | 4/21/2010 | 4/21/2010 | A | PASS |
Doug A Poedy
|
|
|
cal Phone #: ###-####
|
DOC - Permit Finaled | 4/21/2010 | 4/21/2010 | 4/21/2010 | P | PASS |
Doug A Poedy
|
|
|
|
Final | 4/12/2010 | 4/12/2010 | 4/12/2010 | P | FAIL |
Bob Reichert
|
|
|
Cal Phone #: ###-#### called, left correction notice, NEC 210.52(C)(1) shall provide receptacles within 2' of kitchen sink, 210.52(A)(1) shall provide receptacles such that no point along floor line is over 6' from outlet, 406.4 receptacles shall be securely mounted, BCC shall provide full access- possible further corrections at re-inspection time, NOTE: corrections shall be made within 5 working days or further action will be taken such as removal of power
|
Rough-In Permanent Service | 12/28/2009 | 12/28/2009 | 12/28/2009 | P | PASS |
Doug A Poedy
|
|
|
cal Phone #: ###-####. P/S U/G Connect ok. Ok to cover house and garage.
|
Electrical Rough-In | 11/24/2009 | 11/25/2009 | 11/25/2009 | A | PASS |
Doug A Poedy
|
|
|
cal - trench Phone #: ###-####. Ok to cover underground conduits.
|