Final | 2/22/2010 | 2/23/2010 | 2/23/2010 | P | PASS |
Bob Reichert
|
|
|
eric ###-#### correction ok, ok to final, no card to sign,no esc this project, called elec contractor to advise owner that electrical done
|
Final | 2/22/2010 | 2/22/2010 | 2/22/2010 | P | PART |
Bob Reichert
|
|
|
eric Phone #: ###-#### called 414, will reschedule tomorrow for info on plug connected equipment and labelling
|
Final | 2/9/2010 | 2/9/2010 | 2/9/2010 | P | PART |
Bob Reichert
|
|
|
eric Phone #: ###-#### called, left correction notice, NEC 358.30 emt shall be strapped within 3' of panel, BCC4-05-33(A)(B) all equipment shall be listed by a nationally recognized testing laboratory, NOTE: corrections shall be made within 5 working days or further action will be taken, no card to sign
|
Final | 2/5/2010 | 2/8/2010 | 2/8/2010 | A | NH |
Doug A Poedy
|
|
|
Eric ###-####
|
Conference | 2/1/2010 | 2/1/2010 | 2/2/2010 | P | DONE |
Bob Reichert
|
|
|
Eric Phone #: ###-#### went to job, called contractor, contractor has too many loose ends for inspection at this tme- told him to close openings in boxes, get the listings for equipment so we can see them where they are labelled, tighten receptacles, install flex properly, be sure no cord run to air handler, main breaker sized correctly, be sure to provide disconnects as required, provide access to electrical room as it is not to be used for storage, told to call when ready for inspection, no esc this project
|
Final | 2/1/2010 | 2/1/2010 | 2/1/2010 | P | CANC |
Bob Reichert
|
|
|
Eric Phone #: ###-#### see conference
|
Final | 1/22/2010 | 1/22/2010 | 1/22/2010 | P | CANC |
Bob Reichert
|
|
|
eric - please call 1/2 hr prior Phone #: ###-#### see p/s
|
Permanent Service | 1/22/2010 | 1/22/2010 | 1/22/2010 | P | PASS |
Bob Reichert
|
|
|
eric - please call 1/2 hr prior Phone #: ###-#### p/s, exst meter pak, n, ok, 2 meters required, no esc this project
|
Electrical Rough-In | 1/19/2010 | 1/19/2010 | 1/19/2010 | P | PASS |
Bob Reichert
|
|
|
eric - around 2 if possible please Phone #: ###-#### met contractor, p/s u/g rec ok, affixed stickers to 7 existing meters, no esc this project, will call tomorrow for 2 new meters
|
Electrical Rough-In | 12/18/2009 | 12/18/2009 | 12/18/2009 | P | PASS |
Bob Reichert
|
|
|
Eric Phone #: ###-#### called, ok to cover walls only, no esc this project
|
Conference | 12/16/2009 | 12/17/2009 | 12/17/2009 | P | DONE |
Bob Reichert
|
|
|
Eric Phone #: ###-#### talked about service, sub-panels, transformers, no cord for permanent wiring, strapping, no cover before inspection, requires main service disconnect,
|