Final | 2/4/2010 | 2/4/2010 | 2/4/2010 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams corrections made, ok to final, signed occupancy card,
|
Final | 2/3/2010 | 2/4/2010 | 2/4/2010 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams called, left correction notice, NEC 210.8(B)(5) receptacle within 6' of mop sink shall br gfci protected, 725.25 shall remove abandoned lv cables, 110.3(B) listed equipment shall be installed and used in accordance with instructions- receptacles in column shall operate, display rack shall be listed, 400.8 shall not use flexible cable as a substitute for fixed wiring in structure, BCC 4-05033(A),(B) all equipment shall be listed by a nationally recognized testing lab, NOTE: corrections shall be made within 5 working days or further action will be taken
|
Electrical Rough-In | 1/27/2010 | 1/27/2010 | 1/27/2010 | P | PASS |
Bob Reichert
|
|
|
ceiling only Phone #: ###-#### Internet Inspection Request from: Jim Williams ok to cover ceilings
|
Electrical Rough-In | 1/13/2010 | 1/13/2010 | 1/13/2010 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams walls only ok to cover
|