Final | 3/2/2010 | 3/3/2010 | 3/3/2010 | A | PASS |
Bob Reichert
|
|
|
jason Phone #: ###-#### called, left message, ok to final, no esc this project
|
Permanent Service | 1/25/2010 | 1/25/2010 | 1/25/2010 | P | PASS |
Doug A Poedy
|
|
|
Jason Phone #: ###-#### P/S O/H Reconnect ok.
|
Electrical Rough-In | 1/19/2010 | 1/20/2010 | 1/20/2010 | P | PART |
Jack Frank
|
|
|
door should be unlocked but please contact Jason with EPCON electric @###-#### before arrival. thank you! Phone #: ###-#### Internet Inspection Request from: Jason Ewals corr called BMC 4-05-32 violations not retained at service 230.24 clearence for o/h drop from drip loop, 312.5(C) exception ser cable not allowed in conduit, 110.3(B) use manufactures listed breakers only, 250.52(A)(1) grd u/g water pipe note r/i ok
|
Conference | 1/14/2010 | 1/15/2010 | 1/15/2010 | A | DONE |
Doug A Poedy
|
|
|
jason - please call 1/2 hr prior Phone #: ###-####
|