Permit Information
Permit NumberELE10-00147
StatusFinaled
Name HARDLINE ELECTRIC
Site Address 2011 W MOCCASIN CT
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Addition: Underground swimming pool
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/4/20105/5/20105/5/2010APASS
DetailsBob Reichert
Final inspection for pool and spa thanks Inspection requested from web by: Lynn Cable Phone #: ###-#### ok to final
Final5/4/20105/4/20105/4/2010PCANC
DetailsDoug A Poedy
Final inspection for pool and spa thanks Inspection requested from web by: Lynn Cable Phone #: ###-####. Rescheduled
Final4/12/20104/13/20104/12/2010ACANC
DetailsBob Reichert
Swimming pool and hot tub.

Thanks Inspection requested from web by: Lynn Cable Phone #: ###-#### Inspection cancelled from web by: Lynn Cable
Electrical Rough-In3/17/20103/17/20103/17/2010PPASS
DetailsDoug A Poedy
Potting Compound Inspection for the swimming pool Inspection requested from web by: Lynn Cable Phone #: ###-####
Electrical Rough-In2/18/20102/19/20102/19/2010APASS
DetailsBob Reichert
Removed dirt from trench, provided spacing for underground conduits. I will be in the boise area and would like to possibly meet the inspector on site. please give me notice of a time frame. Thanks Inspection requested from web by: Lynn Cable Phone #: ###-#### corrections made, ok to cover u/g
Electrical Rough-In2/18/20102/18/20102/18/2010AFAIL
DetailsBob Reichert
Fixed Conduits ready for underground inspection for hot tub Inspection requested from web by: Lynn Cable Phone #: ###-#### corrections not made, left correction notice, NEC 310.15(B)2(b) shall maintain conduit spacing, BCC shall not cover u/g before inspection, NOTE: corrections shall be made within 5 working days or further action will be taken
Electrical Rough-In2/15/20102/16/20102/16/2010AFAIL
DetailsBob Reichert
Underground Inscpection for above ground Hot Tub
Thanks Inspection requested from web by: Lynn Cable Phone #: ###-#### called contractor, NEC 352.26 there shall not be more than 360 degree total bends in pvc conduit, 310.15(B)2(b) shall maintain conduit spacing
Electrical Rough-In1/25/20101/26/20101/26/2010APASS
DetailsDoug A Poedy
Underground and pool bonding
Thanks Phone #: ###-#### Internet Inspection Request from: Lynn Cable