Final | 5/4/2010 | 5/5/2010 | 5/5/2010 | A | PASS |
Bob Reichert
|
|
|
Final inspection for pool and spa thanks Inspection requested from web by: Lynn Cable Phone #: ###-#### ok to final
|
Final | 5/4/2010 | 5/4/2010 | 5/4/2010 | P | CANC |
Doug A Poedy
|
|
|
Final inspection for pool and spa thanks Inspection requested from web by: Lynn Cable Phone #: ###-####. Rescheduled
|
Final | 4/12/2010 | 4/13/2010 | 4/12/2010 | A | CANC |
Bob Reichert
|
|
|
Swimming pool and hot tub.
Thanks Inspection requested from web by: Lynn Cable Phone #: ###-#### Inspection cancelled from web by: Lynn Cable
|
Electrical Rough-In | 3/17/2010 | 3/17/2010 | 3/17/2010 | P | PASS |
Doug A Poedy
|
|
|
Potting Compound Inspection for the swimming pool Inspection requested from web by: Lynn Cable Phone #: ###-####
|
Electrical Rough-In | 2/18/2010 | 2/19/2010 | 2/19/2010 | A | PASS |
Bob Reichert
|
|
|
Removed dirt from trench, provided spacing for underground conduits. I will be in the boise area and would like to possibly meet the inspector on site. please give me notice of a time frame. Thanks Inspection requested from web by: Lynn Cable Phone #: ###-#### corrections made, ok to cover u/g
|
Electrical Rough-In | 2/18/2010 | 2/18/2010 | 2/18/2010 | A | FAIL |
Bob Reichert
|
|
|
Fixed Conduits ready for underground inspection for hot tub Inspection requested from web by: Lynn Cable Phone #: ###-#### corrections not made, left correction notice, NEC 310.15(B)2(b) shall maintain conduit spacing, BCC shall not cover u/g before inspection, NOTE: corrections shall be made within 5 working days or further action will be taken
|
Electrical Rough-In | 2/15/2010 | 2/16/2010 | 2/16/2010 | A | FAIL |
Bob Reichert
|
|
|
Underground Inscpection for above ground Hot Tub Thanks Inspection requested from web by: Lynn Cable Phone #: ###-#### called contractor, NEC 352.26 there shall not be more than 360 degree total bends in pvc conduit, 310.15(B)2(b) shall maintain conduit spacing
|
Electrical Rough-In | 1/25/2010 | 1/26/2010 | 1/26/2010 | A | PASS |
Doug A Poedy
|
|
|
Underground and pool bonding Thanks Phone #: ###-#### Internet Inspection Request from: Lynn Cable
|