Final | 2/15/2010 | 2/16/2010 | 2/16/2010 | A | PASS |
Jack Frank
|
|
|
Please call 1 hour before inspection to meet on site and discause the survey from the rough in inspection. Inspection requested from web by: Emmet Bushman Phone #: ###-#### ok card signed
|
Electrical Rough-In | 2/9/2010 | 2/10/2010 | 2/10/2010 | A | PASS |
Doug A Poedy
|
|
|
Inspection requested from web by: Emmet Bushman Phone #: ###-####. Left survey. NEC 300.11 A Securing and supporting. Can not use grid support wires for cable support. NEC 300.11 2B Raceways as means of support. Low voltage cables in some areas laying on grid. Please make corrections before cover.
|