Final | 11/18/2010 | 11/18/2010 | 11/18/2010 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Lynn Proctor final ok
|
ELE-Aging Inspection | 10/25/2010 | 10/25/2010 | 10/25/2010 | | DONE |
Bob Reichert
|
|
|
suc
|
ELE-Aging Inspection | 8/24/2010 | 8/24/2010 | 8/24/2010 | | DONE |
Bob Reichert
|
|
|
suc
|
Electrical Rough-In | 6/24/2010 | 6/24/2010 | 6/24/2010 | P | PASS |
Bob Reichert
|
|
|
Lynn Phone #: ###-#### ok to cover soffits
|
Electrical Rough-In | 6/2/2010 | 6/3/2010 | 6/3/2010 | A | PASS |
Bob Reichert
|
|
|
Lynn Phone #: ###-#### ric ok
|
Electrical Rough-In | 2/22/2010 | 2/23/2010 | 2/23/2010 | A | PASS |
Bob Reichert
|
|
|
Lynn ###-#### corrections made, ok to cover u/g
|
Electrical Rough-In | 2/18/2010 | 2/19/2010 | 2/19/2010 | A | FAIL |
Bob Reichert
|
|
|
lynn - underground pvc conduits Phone #: ###-#### called, left message, left correction notice, NEC 300.5(A) raceway shall be 24" under parking area, 300.5(F) backfill shall not contain rocks, 310.15(B)2(b) conduit spacing shall be maintained, NOTE: corrections shall be made within 5 working days or further action will be taken
|