Electrical Rough-In | 3/1/2010 | 3/1/2010 | 3/1/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from, web by: BARRY KENDALL Phone #: ###-#### corrections made, ri ok, no esc
|
Final | 3/1/2010 | 3/1/2010 | 3/1/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: BARRY KENDALL Phone #: ###-#### ok to final, no esc, signed card
|
Final | 2/27/2010 | 3/1/2010 | 3/1/2010 | A | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: BARRY KENDALL Phone #: ###-#### met contractor, left correction notice, NEC 110.12(A) shall close unused openings in box, 210.8(B)(2) all 125v receptacles in kitchen shall be gfci, 330.30(B) shall strap mc within 12" of box, 358.30(A) shall strap emt within 3' of box, 248.30(A) fmc shall be strapped within 12" of box, 300.15 shall provide box at termination of cable, BCC no violations shall be retained, NOTE- corrections shall be made within 5 working days or further action will be taken, NOTE: contractor shall call for ri for re-inspection, no esc this project
|