Final | 5/11/2010 | 5/12/2010 | 5/12/2010 | A | PASS |
Jack Frank
|
|
|
Bill--PLease call at least 30 mins prior to inspection Phone #: ###-####
|
Final | 5/6/2010 | 5/6/2010 | 5/6/2010 | P | FAIL |
Jack Frank
|
|
|
bill - please call 1/2 hr prior so he can meet you there Phone #: ###-#### called violations not corrected 314.28 angle u pulls, remove old GEC from subpanel
|
Final | 4/26/2010 | 4/26/2010 | 4/26/2010 | P | FAIL |
Jack Frank
|
|
|
Bill please call 30 min before going out Phone #: ###-#### corr. called clearence for sub panel 110.26(F)(1), angle pull meter base 314.28, 312.3 subpanel shall be flush with combustible material, 250.24(A)(5) isolate grds and neutrals subpanel
|
Permanent Service | 3/24/2010 | 3/25/2010 | 3/24/2010 | A | PASS |
Jack Frank
|
|
|
Bill Phone #: ###-#### p/s o/h rec. ok
|
Permanent Service | 3/24/2010 | 3/24/2010 | 3/24/2010 | P | FAIL |
Jack Frank
|
|
|
bill Phone #: ###-#### nr
|
Permanent Service | 3/19/2010 | 3/19/2010 | 3/19/2010 | P | FAIL |
Jack Frank
|
|
|
bill Phone #: ###-#### corr grd or bond water system, 250.52 or 104 T310.16 4/0 copper, or 250 alum for com. 200 amp p/s check clearence for service drop
|
Electrical Rough-In | 3/15/2010 | 3/16/2010 | 3/15/2010 | A | PASS |
Jack Frank
|
|
|
Bill - trench Phone #: ###-#### u/g ok
|