Permanent Service | 5/18/2010 | 5/18/2010 | 5/18/2010 | P | PASS |
Jack Frank
|
|
|
Mike Phone #: ###-#### p/s o/h rec. ok
|
Final | 5/18/2010 | 5/18/2010 | 5/18/2010 | P | PASS |
Jack Frank
|
|
|
Mike Phone #: ###-####
|
Rough-In Permanent Service | 5/17/2010 | 5/17/2010 | 5/18/2010 | P | FAIL |
Jack Frank
|
|
|
mike Phone #: ###-#### called all violations not corrected, and new one created terminate GEC at grded bus, and needs 30 breaker for dryer
|
Rough-In Permanent Service | 5/13/2010 | 5/13/2010 | 5/13/2010 | P | FAIL |
Jack Frank
|
|
|
mike Phone #: called remove gas line from below panel, 200.2 terminate GEC at neutral b us, protect #10 awg at 30 amps water heater and dryer, 250.90,92,94 bonding, bond water pipe note insulating joints at WH, seal all unused KOs
|
Permanent Service | 3/18/2010 | 3/18/2010 | 3/18/2010 | P | NH |
Jack Frank
|
|
|
Mike-Code 2001-Service in basement Phone #: ###-#### left message notice posted
|