Temporary Service | 3/22/2010 | 3/22/2010 | 3/22/2010 | P | PASS |
Bob Reichert
|
|
|
Corrections have been made. Inspection requested from web by: Rhonda Yoast Phone #: ###-#### corrections made, t/s o/h n ok, no esc this project
|
Temporary Service | 3/19/2010 | 3/22/2010 | 3/22/2010 | A | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: Rhonda Yoast Phone #: ###-#### called, left correction notice, NEC 110.12(B) there shall be no broken parts, 406.8(B) 15 & 20 A receptacles in wet locations shall be listed weather resistant type
|