Final | 4/9/2010 | 4/12/2010 | 4/12/2010 | A | PASS |
Bob Reichert
|
|
|
robert Phone #: ###-#### ok to final
|
Electrical Rough-In | 3/25/2010 | 3/25/2010 | 3/25/2010 | P | PASS |
Bob Reichert
|
|
|
Robert Phone #: ###-#### corrections made, ric ok
|
Electrical Rough-In | 3/24/2010 | 3/24/2010 | 3/24/2010 | P | FAIL |
Bob Reichert
|
|
|
robert Phone #: ###-#### called, left correction notice, NEC 314.17(C) nm shall be stapled within 8" of box, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 314.20 if combustile material, bobxes shall be flush with finished surface, 225.31 shall supply building disconnect, 110.11 shall not use any material that has a deteriorating effect on conductors, NOTE corrections shall be made within 5 working days
|