Permit Information
Permit NumberELE10-00625
StatusFinaled
Name A M E ELECTRIC
Site Address 1122 S HILTON ST
Project Name 
Customer Number2084598959
ePlanReview 
Description
Electrical Permit - New: Provide and install electrical for a new pump station
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/7/20107/8/20107/7/2010APASS
DetailsJack Frank
mike Phone #: ###-####
Rough-In Permanent Service6/11/20106/14/20106/14/2010PPASS
DetailsDoug A Poedy
MIKES CELL IS ###-####, ALSO DEAN SHOULD BE ON SITE WORKING. Inspection requested from web by: Jamie Winters. P/S U/G Connect ok.
Rough-In Permanent Service6/11/20106/11/20106/11/2010PFAIL
DetailsJack Frank
Jamie''s cell is ###-#### Inspection requested from web by: Jamie Winters
called stillneeds to terminate GEC at neutral (grounded) bus, not the equipment grounding bus
Rough-In Permanent Service6/9/20106/10/20106/10/2010AFAIL
DetailsJack Frank
CORRECTIONS ARE MADE READY FOR REINSPECT. Inspection requested from web by: Mike TenHulzen Phone #: ###-####
grding at p/s not corrected called
Rough-In Permanent Service6/8/20106/9/20106/9/2010AFAIL
DetailsJack Frank
The contact for this is Mike TenHulzen Inspection requested from web by: Jamie Winters Phone #: ###-#### met contr GEC shall terminate at neutral bus, also needs sq D bonding means and equip grd kit, x former grding shall be at X/O terminal not the enclosure
Rough-In Permanent Service5/18/20105/19/20105/19/2010AFAIL
DetailsBob Reichert
ROUGH-IN PERMANENT SERVICE READY IF QUESTIONS PLEASE CALL MIKE AT ###-####. Inspection requested from web by: Mike TenHulzen Phone #: ###-#### called contractor, told that NEC 250.24 shall connect gec to grounded concuctor at servive disconnect, shall provide meter, 310.4(B) parallel conductors shall be same length, check wireway under gear for correct size
Electrical Rough-In4/28/20104/28/20104/28/2010PPASS
DetailsDoug A Poedy
mike - ###-####. Ok to cover underground and attic.
Electrical Rough-In3/29/20103/30/20103/30/2010APART
DetailsJack Frank
UG ready in building only outside building ready later if problems please call Mike at ###-####. On a seperate note there seems to a problem with online service I have reenter a password everytime I use the service can someone please contact me at ###-####. Inspection requested from web by: Mike TenHulzen Phone #: ###-####
u/g inside ok
Final3/26/20103/29/20103/29/2010ACANC
DetailsBob Reichert
UG in pump station inspection UG for remaining work will be ready for inspection Tuesday or Wednesday. If there are any questions or problems please Mike at ###-#### Inspection requested from web by: Mike TenHulzen Phone #: ###-#### wrong type request, see ri
Electrical Rough-In3/29/20103/29/20103/29/2010AFAIL
DetailsBob Reichert
UG in pump station inspection UG for remaining work will be ready for inspection Tuesday or Wednesday. If there are any questions or problems please Mike at ###-#### Inspection requested from web by: Mike TenHulzen Phone #: ###-#### called, left correction notice, NEC 310.15(B)2(b) shall maintain conduit spacing