Final | 6/23/2010 | 6/23/2010 | 6/23/2010 | P | PASS |
Bob Reichert
|
|
|
Dave please call for access Phone #: ###-#### called, ok to final
|
Electrical Rough-In | 4/13/2010 | 4/14/2010 | 4/15/2010 | A | PASS |
Jack Frank
|
|
|
dave Phone #: ###-#### ok
|
Electrical Rough-In | 4/12/2010 | 4/12/2010 | 4/12/2010 | P | FAIL |
Jack Frank
|
|
|
Dave-please call for access Phone #: ###-#### corrections not made wire house as correction posted noted called
|
Electrical Rough-In | 4/7/2010 | 4/7/2010 | 4/7/2010 | P | FAIL |
Jack Frank
|
|
|
dave - please call for access Phone #: ###-#### called told contr all wiring shall meet 2008 NEC too many violations to note
|
Electrical Rough-In | 4/5/2010 | 4/6/2010 | 4/6/2010 | A | NH |
Jack Frank
|
|
|
Dave ###-#### called left phone # notice posted no access
|
Rough-In Permanent Service | 4/5/2010 | 4/5/2010 | 4/5/2010 | P | CANC |
Bob Reichert
|
|
|
please call 1/2 hr prior//Dave ###-####see ri and p/s
|
Permanent Service | 4/5/2010 | 4/5/2010 | 4/5/2010 | P | PASS |
Bob Reichert
|
|
|
please call 1/2 hr prior//Dave ###-#### p/s u/g n ok
|
Electrical Rough-In | 4/5/2010 | 4/5/2010 | 4/5/2010 | P | FAIL |
Bob Reichert
|
|
|
please call 1/2 hr prior//Dave ###-#### called, left correction notice, NEC 314.17(C) shall secure nm cable within 8" of box, #12 and #8, 210.52(C) shall provide receptacle within 2' of sink or in 2' wall space, BCC shall not cover any wiring before inspection, entry, walls, shall add 1 room to permit, NOTE corrections shall be made within 5 working days or further action may be taken
|