Final | 9/1/2010 | 9/2/2010 | 9/2/2010 | P | PASS |
Bob Reichert
|
|
|
Pat Phone #: ###-#### ok final
|
Final | 7/30/2010 | 8/2/2010 | 8/2/2010 | P | FAIL |
Bob Reichert
|
|
|
Pat Phone #: ###-#### left correction notice, 110.12(A) shall close unused openings, 408.4 shall provide circuit schedule, 210.8(A) shall provide gfci by door, 314.20 bar receptacles shall be flush with finished surface, 680.27 shall provide receptacles within 6'-20' of pools, 110.26 shall provide work space about equipment, BCC shall inspect work at bar before cover
|
Rough-In Permanent Service | 4/9/2010 | 4/9/2010 | 4/9/2010 | P | PASS |
Bob Reichert
|
|
|
pat Phone #: ###-#### ric ok, cabana and pool house, p/s u/g n ok
|