Final | 6/3/2010 | 6/3/2010 | 6/4/2010 | P | PASS |
Bob Reichert
|
|
|
Heath Phone #: ###-#### called, ok to final
|
Electrical Rough-In | 4/21/2010 | 4/22/2010 | 4/22/2010 | A | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: Joe Thomas Phone #: ###-#### corrections made, ric ok
|
Electrical Rough-In | 4/20/2010 | 4/21/2010 | 4/21/2010 | A | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: Joe Thomas Phone #: ###-#### called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 300.14 shall provide 6" free conductor length at boxes, 334.23 shall protect cable within 6' of attic access, 250.148 shall ground metal boxes, BCC shall install boxes, NOTE corrections shall be made within 5 working days or further action will be taken
|