Final | 6/16/2010 | 6/16/2010 | 6/16/2010 | A | PASS |
Bob Reichert
|
|
|
GARAGE CODE 1968 THANKS, BILL Inspection requested from web by: Bob Glenn Phone #: ###-#### ok to final
|
Rough-In Permanent Service | 4/30/2010 | 4/30/2010 | 4/30/2010 | P | CANC |
Bob Reichert
|
|
|
Inspection requested from web by: Bob Glenn Phone #: ###-#### wrong type request, see ri
|
Electrical Rough-In | 4/30/2010 | 4/30/2010 | 4/30/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: Bob Glenn Phone #: ###-#### corrections made, ric ok
|
Rough-In Permanent Service | 4/29/2010 | 4/30/2010 | 4/30/2010 | A | CANC |
Bob Reichert
|
|
|
THANKS, HAVE A GOOD DAY!! Inspection requested from web by: Bob Glenn Phone #: ###-#### see ri and p/s
|
Electrical Rough-In | 4/30/2010 | 4/30/2010 | 4/30/2010 | A | FAIL |
Bob Reichert
|
|
|
THANKS, HAVE A GOOD DAY!! Inspection requested from web by: Bob Glenn Phone #: ###-#### called, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.23 shall protect cables within 6' of attic access, Note: shall make corrections within 5 working days
|
Permanent Service | 4/30/2010 | 4/30/2010 | 4/30/2010 | A | PASS |
Bob Reichert
|
|
|
THANKS, HAVE A GOOD DAY!! Inspection requested from web by: Bob Glenn Phone #: ###-#### p/s u/g n ok
|