Final | 8/18/2010 | 8/18/2010 | 8/18/2010 | P | PASS |
Doug A Poedy
|
|
|
|
DOC - Permit Finaled | 8/18/2010 | 8/18/2010 | 8/18/2010 | P | PASS |
Doug A Poedy
|
|
|
|
Final | 8/17/2010 | 8/18/2010 | 8/18/2010 | A | FAIL |
Doug A Poedy
|
|
|
210.8 gfci in kitchen
|
Final | 8/17/2010 | 8/17/2010 | 8/17/2010 | P | CANC |
Jack Frank
|
|
|
John Phone #: ###-#### see added inspection for 08-18-10 AM
|
Permanent Service | 7/30/2010 | 8/2/2010 | 8/2/2010 | A | PASS |
Bob Reichert
|
|
|
John Phone #: ###-#### p/s o/h rec ok
|
Rough-In Permanent Service | 7/30/2010 | 7/30/2010 | 7/30/2010 | P | NR |
Bob Reichert
|
|
|
John Phone #: ###-#### met owner, ground rods not driven in or connnected, needs to add water pipe ground conductor, needs to separate neutral and ground bus in sub-panel, needs to provide abrasion protection for gec
|
Electrical Rough-In | 6/3/2010 | 6/4/2010 | 6/4/2010 | A | PASS |
Doug A Poedy
|
|
|
John Phone #: ###-####
|
Conference | 5/26/2010 | 5/27/2010 | 5/27/2010 | A | DONE |
Doug A Poedy
|
|
|
John at ###-####. Going to leave permit open and do job in stages as money comes in.
|
Conference | 5/24/2010 | 5/25/2010 | 5/25/2010 | A | CANC |
Jack Frank
|
|
|
John Phone #: ###-#### owner already wired house see failed r/i request
|
Electrical Rough-In | 5/24/2010 | 5/25/2010 | 5/25/2010 | A | FAIL |
Jack Frank
|
|
|
John Phone #: ###-#### correction posted owner wired job without having a conference first
|