Temporary Service | 5/26/2010 | 5/26/2010 | 5/26/2010 | A | PASS |
Bob Reichert
|
|
|
corrections made, t/s u/g n ok
|
Temporary Service | 5/25/2010 | 5/25/2010 | 5/26/2010 | P | CANC |
Bob Reichert
|
|
|
Mike Phone #: ###-#### see 5-26-10
|
Temporary Service | 5/24/2010 | 5/25/2010 | 5/25/2010 | A | CANC |
Bob Reichert
|
|
|
mike Phone #: ###-#### called, left correction notice, NEC 406.8(B) all 15 and 20a receptacles in wet locations shall be listed weather resistant type, 250.24(B) shall provide main bonding jumper to equipment ground lug, note; corrections shall be made in 5 working days or further action will be taken
|