ELE-Aging Inspection | 3/30/2011 | 3/30/2011 | 3/30/2011 | | DONE |
Bob Reichert
|
|
|
see doc expire
|
DOC - Permit Expired | 3/30/2011 | 3/30/2011 | 3/30/2011 | A | PASS |
Bob Reichert
|
|
|
talked with 414, ok to expire permit
|
ELE-Aging Inspection | 1/26/2011 | 1/26/2011 | 1/26/2011 | | DONE |
Bob Reichert
|
|
|
suc
|
ELE-Aging Inspection | 11/26/2010 | 11/26/2010 | 11/26/2010 | | DONE |
Bob Reichert
|
|
|
suc
|
Conference | 6/29/2010 | 6/29/2010 | 6/30/2010 | P | DONE |
Doug A Poedy
|
|
|
Doug look up history
|
Final | 6/28/2010 | 6/29/2010 | 6/29/2010 | A | FAIL |
Jack Frank
|
|
|
thanh Phone #: ###-#### all violaltions not corrected 210.11(C) laundry circuit, p/s too small for calculated load kit circuits, and range hood ? 422.16(B)(4) owner needs to hire ele contractor
|
Final | 6/25/2010 | 6/25/2010 | 6/25/2010 | P | FAIL |
Jack Frank
|
|
|
thanh Phone #: ###-#### correction posted tried to explain NEC requirements to owner but so much is in violation, will talk to Doug about job note Bob has already mentioned it to Doug
|
Conference | 6/15/2010 | 6/15/2010 | 6/15/2010 | P | DONE |
Bob Reichert
|
|
|
doan Phone #: ###-#### talked about wiring house, outlet spacing, free length of conductor, 1 1/4", fornt and rear outlets wp type outlets, in-use covers, told owner several times about getting books on wiring requirements, have reservations about owner successfully doing work due to his not understanding english, and he keeps wanting to use #10 awg for wiring, explained that he needs to do load calculation, and explained different wire sizes and breaker sizes, told when to call for ri
|