Final | 8/11/2010 | 8/12/2010 | 8/12/2010 | A | PASS |
Bob Reichert
|
|
|
greg Phone #: ###-#### ok final, signed card
|
Final | 8/9/2010 | 8/10/2010 | 8/10/2010 | A | PART |
Bob Reichert
|
|
|
Greg Phone #: ###-#### called about panel schedules, loose receptacles, receptacles with no power, will recall when done
|
Electrical Rough-In | 7/14/2010 | 7/15/2010 | 7/15/2010 | A | PASS |
Bob Reichert
|
|
|
Greg-ceiling grid inspection please Phone #: ###-#### called, corrections made, ok cover ceiling
|
Electrical Rough-In | 7/13/2010 | 7/14/2010 | 7/14/2010 | A | FAIL |
Bob Reichert
|
|
|
Greg this is to inspect the celing tile Phone #: ###-#### called, left correction notice, NEC 314.25 all boxes shall be closed with covers, 300.11 cables and raceways shall not be supported by ceiling grids,725.25 abandoned low voltage cables shall be removed, BCC tiles shall be removed to inspect each fixture and any boxes in ceiling, NOTE; corrections shall be made within 5 working days or further action will be taken
|
Electrical Rough-In | 6/30/2010 | 7/2/2010 | 7/2/2010 | A | PASS |
Bob Reichert
|
|
|
Brett Phone #: ###-#### walls only ok to cover
|