Final | 8/5/2010 | 8/6/2010 | 8/6/2010 | A | PASS |
Bob Reichert
|
|
|
Access is a lockbox at front door with code 5858. Contact for job is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery ok final, signed card
|
Electrical Rough-In | 8/4/2010 | 8/5/2010 | 8/5/2010 | A | PASS |
Jack Frank
|
|
|
Ceiling Inspection of 2 front office areas. Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery
|
Permanent Service | 7/26/2010 | 7/26/2010 | 7/26/2010 | P | PASS |
Doug A Poedy
|
|
|
This is a service inspection. If tenant space is locked, there is a lock-box at front door with the code 5858. The contact on this job is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery. P/S Connect ok.
|
Electrical Rough-In | 7/7/2010 | 7/8/2010 | 7/8/2010 | A | PASS |
Bob Reichert
|
|
|
Re-inspect for rough of walls. Contact is Jay Sprik. Inspection requested from web by: Richard Montgomery Phone #: ###-#### corrections made, ok cover walls only
|
Electrical Rough-In | 7/7/2010 | 7/7/2010 | 7/7/2010 | P | FAIL |
Bob Reichert
|
|
|
Electrical rough for walls. Contact is Jay Sprik. Inspection requested from web by: Richard Montgomery Phone #: ###-#### called, left correction notice, NEC 300.14 at least 6' free conductor shall be provided where conductor emerges from cable, 110.26(F)(1) there shall be no foreign piping in dedicated equipment space
|