Temporary Service | 7/13/2010 | 7/13/2010 | 7/13/2010 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman corrections made, t/s o/h n ok
|
Temporary Service | 7/12/2010 | 7/12/2010 | 7/12/2010 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman called, left correction notice, NEC 110.12(B) there shall be no broken parts, 250v recpt, 406.8(B) 15 & 20a recpts shall be listed weather resistant, shall affix job id sticker, NOTE corrections shall be made within 5 working days
|