Final | 8/19/2010 | 8/19/2010 | 8/19/2010 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Lynn Cable ok, signed card
|
Final | 8/18/2010 | 8/18/2010 | 8/18/2010 | P | NR |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Lynn Cable called, needs to hook up equipment, check for permanent hook up for wall mounted equipment, low voltage on grid, abrasion protection for low voltage and wall mounted equipment,
|
Electrical Rough-In | 8/3/2010 | 8/4/2010 | 8/4/2010 | P | PASS |
Bob Reichert
|
|
|
Above grid inspection Job-site contact Kotton at ###-#### Phone #: ###-#### >> Inspection requested via web by Lynn Cable ok cover ceiling
|
Electrical Rough-In | 7/14/2010 | 7/15/2010 | 7/15/2010 | A | PASS |
Bob Reichert
|
|
|
Job site contact-Kotton-###-#### Phone #: ###-#### >> Inspection requested via web by Lynn Cable corrections made, ri walls only ok
|
Electrical Rough-In | 7/13/2010 | 7/14/2010 | 7/14/2010 | P | FAIL |
Bob Reichert
|
|
|
Job Contact-Kotton-###-####. Cover inspection for walls. Located on Second floor in the south-east corner of bulding Thanks Phone #: ###-#### >> Inspection requested via web by Lynn Cable called, left correction notice, NEC 300.4(D) cables and raceways shall be 1 1/4" from edge of framing members, BCC there shall be no wiring in channels of framing members, Note; corrections shall be made within 5 working days or further action will be taken
|