Final | 8/16/2010 | 8/16/2010 | 8/16/2010 | P | PASS |
Bob Reichert
|
|
|
les Phone #: ###-#### corrections made, ok final, signed card
|
Final | 8/13/2010 | 8/13/2010 | 8/13/2010 | P | PART |
Bob Reichert
|
|
|
>> Inspection requested via web by les chaney called, needs mc and emt strapping,gfci within 6' of sink, switch plate, signed t/o card only
|
Electrical Rough-In | 8/4/2010 | 8/4/2010 | 8/4/2010 | P | PASS |
Bob Reichert
|
|
|
Les Chaney Phone #: ###-#### corrections made, ri walls only ok
|
Electrical Rough-In | 8/3/2010 | 8/4/2010 | 8/4/2010 | A | FAIL |
Bob Reichert
|
|
|
les ###-#### called, left corredction notice, NEC 300.4(A)&(D) edge of bored holes and cables shall be 1 1/4" from edge of framing members, 110.12(A) shall close unused openings, 330.30(A) shall secure mc cable within 12'" of box, 358.30(A) shall secure ent within3' of box, NOTE corrections shall be made within 5 working days or further action will be taken
|
Electrical Rough-In | 8/2/2010 | 8/3/2010 | 8/3/2010 | P | NR |
Bob Reichert
|
|
|
>> Inspection requested via web by les chaney talked to contractor, reschedule for am
|