Permit Information
Permit NumberELE10-01705
StatusFinaled
Name PRO-TEC SYSTEMS
Site Address 6306 W FOGGY BOTTOM DR
Project Name 
Customer Number1827
ePlanReview 
Description
Electrical Permit - New: New Construction
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/12/20109/13/20109/13/2010APASS
DetailsJack Frank
Phone #: ###-#### >> Inspection requested via web by Josh Craig
Final9/9/20109/9/20109/9/2010PFAIL
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Josh Craig talked with contractor, left correction notice, NEC 408.4 circuit directory shall agree with panel marks, 110.26 shall provide work space in front of panel, 210.52(A)(2) shall provide convenience outlet under bar, BCC laundry room receptacles shall operate correctly, NOTE corrections shall be made within 5 working days
Permanent Service8/10/20108/11/20108/11/2010APASS
DetailsDoug A Poedy
Phone #: ###-#### >> Inspection requested via web by Josh Craig. P/S U/G Connect ok.
Rough-In Permanent Service8/3/20108/4/20108/4/2010PCANC
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Josh Craig see ri
Electrical Rough-In8/4/20108/4/20108/4/2010PPASS
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Josh Craig n ri ok