Final | 10/4/2010 | 10/5/2010 | 10/5/2010 | A | PASS |
Bob Reichert
|
|
|
>> Inspection requested via web by steve cooper corrections made, t/s u/g n ok
|
Temporary Service | 9/15/2010 | 9/15/2010 | 9/16/2010 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by steve cooper called, left correction notice, NEC 110.12(B) there shall be no broken parts, 406.8(B) receptacles shall be listed wr type, 250.53(G) upper end of electrode shall be flush with or below ground, 110.26(A) shall provide working space, BCC job id sticker shall be posted, shall clean interior debris from panel, fee due
|