Final | 9/23/2010 | 9/23/2010 | 9/23/2010 | P | CANC |
Bob Reichert
|
|
|
Bob will have corrections made this morning and ready this afternoon Thanks Dave Phone #: ###-#### >> Inspection requested via web by jason shifflett wrong type request, see t/s
|
Temporary Service | 9/23/2010 | 9/23/2010 | 9/23/2010 | P | PASS |
Bob Reichert
|
|
|
Bob will have corrections made this morning and ready this afternoon Thanks Dave Phone #: ###-#### >> Inspection requested via web by jason shifflett corrections made, t/s u/g n ok
|
Temporary Service | 9/22/2010 | 9/22/2010 | 9/22/2010 | P | FAIL |
Bob Reichert
|
|
|
Dave ###-#### called, left correction notice, NEC 406.8(B) shall install WR receptacle, 110.12(B) there shall be no foreign material in panel, 210.53(G) upper end of electrode shall be flush with or below ground, 312.5 all conductors entering enclosure shall have abrasion protection
|