Final | 12/22/2010 | 12/23/2010 | 12/23/2010 | A | PASS |
Bob Reichert
|
|
|
corrections made, ok final, signed card
|
Final | 12/22/2010 | 12/22/2010 | 12/22/2010 | P | CANC |
Jack Frank
|
|
|
2nd final for corrections. Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins see added am request
|
Final | 12/20/2010 | 12/21/2010 | 12/21/2010 | P | FAIL |
Bob Reichert
|
|
|
Please call to make sure some one is there to meet with you. Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins left correction notice, NEC 400.8 flexible cords shall not be used as a substitute for fixed wiring of structure, BCC 4-05-33(A),(B) all equipment shall be listed by a nationally recognized testing laboratory
|
Conference | 12/20/2010 | 12/20/2010 | 12/20/2010 | P | DONE |
Jack Frank
|
|
|
conference walk in cooler listing
|
Conference | 12/14/2010 | 12/14/2010 | 12/14/2010 | P | DONE |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins left correction notice, NEC 210.8(B) kitcvhen receptacles shall be gfci protected
|
Electrical Rough-In | 12/2/2010 | 12/2/2010 | 12/2/2010 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins ok cover ceiling, find listing for ups and cooler
|
Electrical Rough-In | 11/24/2010 | 11/24/2010 | 11/24/2010 | P | PART |
Bob Reichert
|
|
|
Tom Phone #: ###-#### met electrician, ok to do most of ceiling borders only
|
Electrical Rough-In | 11/17/2010 | 11/17/2010 | 11/17/2010 | P | PASS |
Bob Reichert
|
|
|
tom - underground Phone #: ###-#### ok cover u/g
|
Permanent Service | 11/12/2010 | 11/12/2010 | 11/12/2010 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins p/s u/g n ok
|
Electrical Rough-In | 10/26/2010 | 10/26/2010 | 10/26/2010 | P | PASS |
Jack Frank
|
|
|
tom Phone #: ###-#### walls soffit and hard ceilings
|
Electrical Rough-In | 9/23/2010 | 9/23/2010 | 9/23/2010 | P | PASS |
Jack Frank
|
|
|
tom - underground Phone #: ###-#### ok
|