Final | 1/18/2011 | 1/19/2011 | 1/19/2011 | A | PASS |
Bob Reichert
|
|
|
Contact: Mark Knight Phone #: ###-#### >> Inspection requested via web by Deb Gooden ok final, signed card
|
Electrical Rough-In | 1/10/2011 | 1/11/2011 | 1/11/2011 | P | PASS |
Bob Reichert
|
|
|
Contact: Mark Knight - ceiling inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden ok cover ceilings
|
Permanent Service | 12/29/2010 | 12/29/2010 | 12/29/2010 | P | PASS |
Jack Frank
|
|
|
Contact: Mark Knight - late PM inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden needs #3 equip grds for parallel feeder to 480V subpanel 250.122 p/s u/g new ok
|
Permanent Service | 12/28/2010 | 12/29/2010 | 12/29/2010 | A | FAIL |
Jack Frank
|
|
|
contact Mark Knight Phone #: ###-#### >> Inspection requested via web by Deb Gooden not ready
|
Electrical Rough-In | 12/23/2010 | 12/27/2010 | 12/27/2010 | A | PASS |
Daryl DeGrange
|
|
|
Contact: Mark Knight Phone #: ###-#### >> Inspection requested via web by Deb Gooden ri ok office area
|
Electrical Rough-In | 12/23/2010 | 12/23/2010 | 12/27/2010 | P | PASS |
Daryl DeGrange
|
|
|
ri ok cover of office area
|
Electrical Rough-In | 11/8/2010 | 11/8/2010 | 11/8/2010 | P | PASS |
Bob Reichert
|
|
|
Contact: Garrett Collins - underground inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden corrections made, u/g ok
|
Electrical Rough-In | 11/5/2010 | 11/8/2010 | 11/8/2010 | A | FAIL |
Bob Reichert
|
|
|
Contact: Garrett Collins - underground inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden called, left correction notice, NEC 310.15(B)2(b) shall maintain conduit spacing, 300.5 (F) shall not allow rocks for backfill that would damage raceways or interfere with compaction
|
Electrical Rough-In | 10/22/2010 | 10/22/2010 | 10/22/2010 | P | PASS |
Doug A Poedy
|
|
|
Contact: Garrett Collins - underground inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden. Underground ok.
|
Electrical Rough-In | 10/20/2010 | 10/21/2010 | 10/21/2010 | P | NR |
Bob Reichert
|
|
|
Contact: Garrett Collins - underground inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden only small part of u/g done, will call in later
|