ELE-Aging Inspection | 3/2/2011 | 3/2/2011 | 3/2/2011 | | DONE |
Bob Reichert
|
|
|
see final
|
Final | 3/2/2011 | 3/2/2011 | 3/2/2011 | A | PASS |
Bob Reichert
|
|
|
ok final
|
Permanent Service | 12/28/2010 | 12/29/2010 | 12/29/2010 | P | PASS |
Daryl DeGrange
|
|
|
All the repairs have been corrected and is ready for an inspection, please call for any questions, thanks, Terry W. Phone #: ###-#### >> Inspection requested via web by Stephen Kren p/s o/h rec ok
|
Permanent Service | 12/13/2010 | 12/13/2010 | 12/13/2010 | P | FAIL |
Bob Reichert
|
|
|
Please call for any questions, thanks, Terry W. Phone #: ###-#### >> Inspection requested via web by Stephen Kren called, left correction notice, NEC 110.26 shall provide workspace about service, 110.12(A) unused openings shall be closed, 250.24 shall ground ac service at point of grounded service conductor termination, 250.52(A)(1) shall provide metal underground water pipe as main grounding electrode and augment with 2 ground rods 6' apart, 314.15 fittings shall be listed for use in wet locations, BCC no violations shall be retained,
|