Final | 3/11/2011 | 3/11/2011 | 3/11/2011 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson final ok
|
Final | 3/3/2011 | 3/4/2011 | 3/4/2011 | A | NR |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson No access to garage do to wet paint on floor- plates missing through-out house.
|
Electrical Rough-In | 1/25/2011 | 1/25/2011 | 1/25/2011 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson ri ok
|
Electrical Rough-In | 1/12/2011 | 1/13/2011 | 1/13/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson called, left message, left correction notice, NEC 334.30 shall staple nm cable within 12" of box, 210.52(B) small appliance branch circuits shall be on 20A circuits, 210.8(A)(7) shall provide gfci protection within 6' of sinks
|
Permanent Service | 12/13/2010 | 12/13/2010 | 12/13/2010 | P | PASS |
Daryl DeGrange
|
|
|
Installing temporary power at existing perm service, Disconnecting all existing wiring feeding home, addressing proper grounding. Phone #: ###-#### >> Inspection requested via web by Therrin Robertson t/p u/g rec ok
|