Final | 2/9/2011 | 2/9/2011 | 2/9/2011 | P | PASS |
Bob Reichert
|
|
|
Office addition Phone #: ###-#### >> Inspection requested via web by Tim Lawrence ok final, signed card
|
Final | 2/7/2011 | 2/9/2011 | 2/9/2011 | A | NH |
Bob Reichert
|
|
|
Electrical final on office spaces Phone #: ###-#### >> Inspection requested via web by Tim Lawrence talked with contractor, will recall
|
Final | 2/2/2011 | 2/7/2011 | 2/7/2011 | P | FAIL |
Bob Reichert
|
|
|
Requesting Electrical Final on new office addition. Phone #: ###-#### >> Inspection requested via web by Tim Lawrence called, left correction notice, NEC 210.8(B)(5) shall provide gfci protection for receptacles within 6' of sink-15and 20A, BCC shall provide dual level switching per plans for office lighting, BCC panel schedule shall be correct per NEC 408.4
|
Electrical Rough-In | 1/5/2011 | 1/6/2011 | 1/6/2011 | P | PASS |
Bob Reichert
|
|
|
Electrical Rough-in on new office addition. Phone #: ###-#### >> Inspection requested via web by Tim Lawrence corrections made, ri ok
|
Electrical Rough-In | 1/3/2011 | 1/4/2011 | 1/4/2011 | P | FAIL |
Bob Reichert
|
|
|
Electrical Rough for new office building and Loading dock addition Phone #: ###-#### >> Inspection requested via web by Tim Lawrence called, NEC 300.14, 6" free conductor length at switch, 300.4 (A) edge of bored holes shall be 1 1/4" from edge of framing members, 330.30(A) shall secure mc cable within 6" of box
|