Final | 6/16/2011 | 6/16/2011 | 6/16/2011 | P | PASS |
Bob Reichert
|
|
|
corrections made, ok final, no card
|
Final | 4/5/2011 | 4/5/2011 | 4/5/2011 | P | PART |
Bob Reichert
|
|
|
John Phone #: ###-#### left correction notice, NEC 110.26(C) shall provide egress doors and panic bars for electrical room, 110.12(A) shall close unused openings in furniture, signed t/o card
|
Final | 4/1/2011 | 4/1/2011 | 4/1/2011 | P | DONE |
Jack Frank
|
|
|
john Phone #: ###-#### ok for office fixtures
|
Final | 3/23/2011 | 3/23/2011 | 3/23/2011 | P | PART |
Bob Reichert
|
|
|
Final inspection for floors 1-3. Please call John at ###-####. Phone #: ###-#### >> Inspection requested via web by John Campbell all but furniture for 1,2,3 floors ok
|
Electrical Rough-In | 3/17/2011 | 3/17/2011 | 3/17/2011 | P | PASS |
Bob Reichert
|
|
|
basement inspection. Please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell ok cover basement ceiling anop
|
Electrical Rough-In | 3/10/2011 | 3/11/2011 | 3/11/2011 | A | PASS |
Bob Reichert
|
|
|
basement ceiling. Please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell ok cover basement ceiling anop
|
Electrical Rough-In | 3/8/2011 | 3/8/2011 | 3/8/2011 | P | PASS |
Bob Reichert
|
|
|
1st floor ceiling. Please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell 1st floor ceiling ok cover anop
|
Electrical Rough-In | 3/7/2011 | 3/7/2011 | 3/7/2011 | P | PART |
Bob Reichert
|
|
|
1st floor ceiling. Please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell ok ceiling anop
|
Electrical Rough-In | 2/28/2011 | 2/28/2011 | 2/28/2011 | P | PASS |
Bob Reichert
|
|
|
2nd floor ceiling. Please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell ok cover ceiling and floor 2nd floor anop
|
Electrical Rough-In | 2/23/2011 | 2/24/2011 | 2/24/2011 | A | PART |
Bob Reichert
|
|
|
2nd floor ceiling... Please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell ok to do borders 2nd fl only, will check lv wiring for plenum rating
|
Electrical Rough-In | 2/22/2011 | 2/22/2011 | 2/22/2011 | P | PASS |
Bob Reichert
|
|
|
ceiling rough-in. Please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell 3rd floor ceiling and floor ok to cover anop
|
Electrical Rough-In | 2/18/2011 | 2/18/2011 | 2/18/2011 | P | PART |
Bob Reichert
|
|
|
ceiling rough-in... please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell 3rd floor ceiling ok anop, left correction notice NEC 725 shall remove abandoned lv cables
|
Rough-In Permanent Service | 2/14/2011 | 2/14/2011 | 2/14/2011 | P | CANC |
Bob Reichert
|
|
|
Please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell see ri
|
Electrical Rough-In | 2/14/2011 | 2/14/2011 | 2/14/2011 | P | PART |
Bob Reichert
|
|
|
Please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell looked at three floors for ri items - floors and ceilings
|
Electrical Rough-In | 1/20/2011 | 1/21/2011 | 1/21/2011 | A | PART |
Bob Reichert
|
|
|
1st Floor wall rough-in. Please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell walls east 1/2 1st floor ok cover
|
Electrical Rough-In | 1/18/2011 | 1/18/2011 | 1/18/2011 | P | PART |
Bob Reichert
|
|
|
wall rough-in - please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell walls only, 2&3 floor
|