Final | 5/3/2011 | 5/3/2011 | 5/3/2011 | P | PASS |
Bob Reichert
|
|
|
Should be open if not garage code is JAYO enter Phone #: ###-#### >> Inspection requested via web by Zane Robertson ok to final
|
Rough-In Permanent Service | 3/16/2011 | 3/17/2011 | 3/17/2011 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Zane Robertson corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 3/15/2011 | 3/15/2011 | 3/15/2011 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Zane Robertson called, left correction notice, NEC 250.148 all ground conductors shall be connected in box, 334.30 nm cable shall not be stapled on edge, BCC all boxes shall be wired, NOTE: shall locate attic access, shall post esc card
|
Electrical Rough-In | 2/18/2011 | 2/22/2011 | 2/22/2011 | A | PASS |
Bob Reichert
|
|
|
Zane Phone #: ###-#### u/g only ok
|