Final | 5/20/2011 | 5/20/2011 | 5/20/2011 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson corrections made, ok final
|
Final | 5/17/2011 | 5/17/2011 | 5/17/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Zane Robertson called, bath lights, recepts, a/c, panel cover
|
Rough-In Permanent Service | 3/28/2011 | 3/29/2011 | 3/29/2011 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson rough-in p/s u/g n ok
|
Rough-In Permanent Service | 3/27/2011 | 3/28/2011 | 3/28/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 334.30 nm cable shall be secured within 12" of box, BCC all make-up shall be done, all cable shall terminate in boxes, no framing changes after wiring approval
|
Electrical Rough-In | 3/11/2011 | 3/11/2011 | 3/11/2011 | A | PASS |
Bob Reichert
|
|
|
In slab conduit to island Phone #: ###-#### >> Inspection requested via web by Therrin Robertson u/g ok for island
|