Final | 8/25/2011 | 8/25/2011 | 8/25/2011 | A | PASS |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 8/25/2011 | 8/25/2011 | 8/25/2011 | | DONE |
Jack Frank
|
|
|
|
Permanent Service | 3/15/2011 | 3/15/2011 | 3/15/2011 | P | PASS |
Daryl DeGrange
|
|
|
reinspect all corrections made Phone #: ###-#### >> Inspection requested via web by chris burke p/s o/h rec ok
|
Final | 3/9/2011 | 3/10/2011 | 3/10/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by chris burke called, left message, left correction notice, NEC 240.24 center of operating handle shall not be over 6'-7" above floor, 250.52 shall utilize incoming water pipe as ground and within 5' of entering structure, 250.24 shall connect grounding electrode conductor to grounded conductor in service, NOTE: corrections shall be made within 5 working days or further action will be taken, such as removal of power
|