Permit Information
Permit NumberELE11-00521
StatusFinaled
Name R M E INC
Site Address 3527 S FEDERAL WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: Install outlets & lighting per prints
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/3/20116/6/20116/6/2011APASS
DetailsBob Reichert
Mike. Call prior to heading to site. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy corrections made, no card, ok final
Final6/2/20116/2/20116/2/2011PFAIL
DetailsBob Reichert
Scott Phone #: ###-#### >> Inspection requested via web by Sean DeLacy met contractor, left correction notice, NEC 400.5(A) shall not exceed ampacity of flexible cord (cooler), 400.8(1) shall not use flexible cord as a substitute for fixed wiring of structure, BCC 4-05-33(A)(B) shall provide only equipment that is listed by a nationally recognized testing laboratory
Final6/1/20116/2/20116/2/2011AFAIL
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Tyler Bowen no access, can't see labels, called to reschedule and meet wireman
Electrical Rough-In3/30/20113/31/20113/31/2011APASS
DetailsDaryl DeGrange
Mike Phone #: ###-#### >> Inspection requested via web by Sean DeLacy rough-in ok cover wall
Electrical Rough-In3/23/20113/24/20113/24/2011APASS
DetailsBob Reichert
SCOTT Phone #: ###-#### >> Inspection requested via web by Sean DeLacy called, told about conduit spacing, u/g only ok to cover