Final | 4/12/2011 | 4/12/2011 | 4/12/2011 | P | PASS |
Jack Frank
|
|
|
we will be ready for a final inspection this after noon Thanks Dave Phone #: ###-#### >> Inspection requested via web by jason shifflett
|
Permanent Service | 4/12/2011 | 4/12/2011 | 4/12/2011 | P | PASS |
Jack Frank
|
|
|
>> Inspection requested via web by jason shifflett p/s o/h rec. ok
|
Final | 4/7/2011 | 4/7/2011 | 4/7/2011 | P | FAIL |
Jack Frank
|
|
|
House will be open made sure grounding and bonding are suffient and Range and Dryer are 4-wire Recpacles. Phone #: ###-#### >> Inspection requested via web by jason shifflett called 310.15 derate conductors, 200.6 shall not ID #6 or smaller neutral 110.3(B) use only manufacture's listed breakers, 110.26 (F)(2) provide required work space note panel not allowed over stairwell, cover for LB, connector for GEC
|