Final | 5/24/2011 | 5/25/2011 | 5/25/2011 | P | PASS |
Bob Reichert
|
|
|
Emmett Phone #: ###-#### ok final, signed card
|
Final | 5/20/2011 | 5/23/2011 | 5/20/2011 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman Inspection cancelled from web by: Emmet Bushman
|
Electrical Rough-In | 5/12/2011 | 5/13/2011 | 5/13/2011 | A | PASS |
Bob Reichert
|
|
|
grid / ceiling inspection Phone #: ###-#### >> Inspection requested via web by Emmet Bushman ok cover ceiling
|
Rough-In Permanent Service | 4/21/2011 | 4/22/2011 | 4/22/2011 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman corrections made, ri ok, p/s exst meter pak n ok
|
Rough-In Permanent Service | 4/21/2011 | 4/21/2011 | 4/21/2011 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman called, left correction notice, NEC 250.86 shall provide grounding for metal boxes, 330.30(B) shall secure mc cable within 12" of box
|