Final | 5/8/2012 | 5/9/2012 | 5/9/2012 | P | PASS |
Bob Reichert
|
|
|
Talked to home owners. They are suppose to leave the dog in the house in the afternoon. Phone #: ###-#### >> Inspection requested via web by Lynn Cable ok final
|
Final | 5/8/2012 | 5/8/2012 | 5/8/2012 | P | NH |
Bob Reichert
|
|
|
Please call first- Lynn ###-#### Phone #: ###-#### >> Inspection requested via web by Lynn Cable called, dogs loose in back, contractor tried to get hold of owner, will re- call
|
ELE-Aging Inspection | 2/17/2012 | 2/17/2012 | 2/17/2012 | | DONE |
Bob Reichert
|
|
|
called contractor to call for final if done
|
Electrical Rough-In | 4/28/2011 | 4/29/2011 | 4/29/2011 | A | PASS |
Bob Reichert
|
|
|
Verified finish grade and made sure high voltage conduits have 18" of cover, low voltage GFCI protected conduits 12" of cover. Had to bust out lava rocks on south end of trench. Finish grade is approx 2" below siding.
Thanks Phone #: ###-#### >> Inspection requested via web by Lynn Cable corrections made, ok cover u/g
|
Electrical Rough-In | 4/28/2011 | 4/28/2011 | 4/28/2011 | A | PART |
Bob Reichert
|
|
|
Underground inspection and rough in/cover inspection for patio''s in back yard Phone #: ###-#### >> Inspection requested via web by Lynn Cable called, left correction notice,NEC 300.5 pvc shall be 18" deep, 250.86 shall ground metal boxes, BCC shall mount boxes and provide make-up, shall not cover raceways prior to inspection, ok cover columns and ceilings
|