ELE-Aging Inspection | 11/27/2012 | 11/27/2012 | 11/29/2012 | | DONE |
Bob Reichert
|
|
|
house has power, still failed inspection, see doc expire
|
DOC - Permit Expired | 11/29/2012 | 11/29/2012 | 11/29/2012 | A | PASS |
Bob Reichert
|
|
|
power not re-connected per process, inspections not requested, no formal final done, ok doc expire per city policy due to time
|
ELE-Aging Inspection | 8/28/2012 | 8/28/2012 | 8/28/2012 | | DONE |
Bob Reichert
|
|
|
still under construction
|
ELE-Aging Inspection | 5/28/2012 | 5/28/2012 | 5/30/2012 | | DONE |
Bob Reichert
|
|
|
still failed, still under construction
|
ELE-Aging Inspection | 2/27/2012 | 2/27/2012 | 2/29/2012 | | DONE |
Bob Reichert
|
|
|
still under construction
|
Permanent Service | 5/11/2011 | 5/16/2011 | 5/16/2011 | P | FAIL |
Bob Reichert
|
|
|
We have repaired the Service Riser that was damaged. The Home Owner will be home to allow you access to the Service her name is Rebecca. If you have any questions, please feel free to contact us. PLEASE FINAL THIS INSPECTION AFTER THE PERMANENT SERVICE IF IT IS OK. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate called, left correction notice, NEC 250.24(A) shall connect grounding electrode conductor to grounded conductor at service, 250.52(A) shall connect interior water pipe within 5' of entering structure and supplement with 2 ground rods
|