Temporary Service | 5/23/2011 | 5/23/2011 | 5/23/2011 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Celinda Winters t/s u/g n ok
|
Final | 5/21/2011 | 5/23/2011 | 5/23/2011 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Celinda Winters Inspection cancelled from web by: Celinda Winters
|
Final | 5/19/2011 | 5/20/2011 | 5/20/2011 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Celinda Winters NO identification tag,NEC250.64 Shalluse metallic conector listed for grounding and bonding or use non-metallic conector,NEC406.8A inuse covers missing,NEC406.8B weather resistant receptacles,Nec 352.10(F) Exsposed PVC conduit shall be schedule 80,NEC352.30(A) PVC conduit shall be fastened within 3ft of conduit termination.
|