Permit Information
Permit NumberELE11-00994
StatusFinaled
Name XTREME ELECTRIC INC
Site Address 1520 N COLE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
service for a sno shack - $1,000 per initial cert of value
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/20/20115/23/20115/23/2011APASS
DetailsBob Reichert
Tyrel Phone #: ###-#### corrections made, ok final
Final5/19/20115/20/20115/20/2011ACANC
DetailsBob Reichert
Permanent Service5/19/20115/19/20115/19/2011PPASS
DetailsBob Reichert
Mitch PLEASE CALL 30 MIN BEFORE GOING OUT Phone #: ###-#### p/s o/h n ok, called contractor, this is conditional before final that equipment is braced for available fault current, conduit is strapped, ground bar is installed in ice box panel
Conference5/19/20115/19/20115/19/2011PDONE
DetailsBob Reichert
talked about service, feeding ice machine, bringing sno-shack up to code, told contractor we would not need access to shack until final
Permanent Service5/17/20115/18/20115/18/2011AFAIL
DetailsBob Reichert
blake Phone #: ###-#### called, left message, left correction notice, BCC 4-05-33)A),(B) all equipment shall be listed by a nationally recognized testing lab, shall affix job id sticker, riser shall be minimum 2", NEC 250.56 shall install 2 ground rods, 312.5 all conductors entering enclosure shall have abrasion protection, 200.7 shall not use white wire for phase conductor, 400.8 so cord shall not be used as a substitute for fixed wiring for structure, 250.32(B) shall carry ground to separate structure disconnect