Temporary Service | 6/3/2011 | 6/6/2011 | 6/6/2011 | A | PASS |
Jack Frank
|
|
|
George Phone #: ###-#### t/s o/h new ok
|
Temporary Service | 6/1/2011 | 6/1/2011 | 6/1/2011 | P | FAIL |
Bob Reichert
|
|
|
George Phone #: ###-#### called, left correction notice, NEC 250.53(G) upper end ground rod shall be flush with or below ground level, 312.5 all conductors entering enclosure shall have abrasion protection, 406.8(B) 125v receptacle shall be listed weather-resistant, BCC shall post job id sticker
|